$ ControlNet Electronic Data Sheet For FR-A700 $ $ $ Modification History $ v1.1 2006-01-21 [File] DescText = "EDS for A700"; CreateDate = 01-21-2006; CreateTime = 00:00:00; ModDate = 01-20-2006; ModTime = 00:00:00; Revision = 1.1; [Device] VendCode = 161; VendName = "Mitsubishi Electric"; ProdType = 2; ProdTypeStr = "AC Drive"; ProdCode = 52; MajRev = 1; MinRev = 1; ProdName = "A700"; Catalog = "FR-A7NCN"; [Device Classification] Class1 = 1_RSNetWorx_Adapter; Class2 = ControlNet; [Port] Port1 = ControlNet_Redundant, $ port type name "Port A", $ name of port "20 F0 24 01", $ instance one of the ControlNet object 2; $ port number [Connection Manager] Connection1 = 0x04010002, $ trigger & transport $ 0-15 = supported transport classes (class 1) $ 16 = cyclic (1 = supported) $ 17 = change of state (0 = not supported) $ 18 = on demand (0 = not supported) $ 19-23 = reserved (must be zero) $ 24-27 = exclusive owner $ 28-30 = reserved (must be zero) $ 31 = client 0 (don't care for classes 0 and 1) 0x44244405, $ point/multicast & priority & realtime format $ 0 = O=>T fixed (1 = supported) $ 1 = O=>T variable (0 = not supported) $ 2 = T=>O fixed (1 = supported) $ 3 = T=>O variable (0 = not supported) $ 4-7 = reserved (must be zero) $ 8-10 = O=>T header (4 byte run/idle) $ 11 = reserved (must be zero) $ 12-14 = T=>O header $ 15 = reserved (must be zero) $ 16-19 = O=>T point-to-point $ 20-23 = T=>O multicast $ 24-27 = O=>T scheduled $ 28-31 = T=>O scheduled ,4,Assem21, $ O=>T RPI,Size,Format ,4,Assem71, $ T=>O RPI,Size,Format ,, $ config part 1 (dynamic assemblies) ,, $ config part 2 (module configuration) "Instance 21 71", $ connection name "", $ Help string "20 04 24 01 2C 15 2C 47"; $ exclusive output path (instance 0x71) Connection2 = 0x04010002, $ trigger & transport $ 0-15 = supported transport classes (class 1) $ 16 = cyclic (1 = supported) $ 17 = change of state (0 = not supported) $ 18 = on demand (0 = not supported) $ 19-23 = reserved (must be zero) $ 24-27 = exclusive owner $ 28-30 = reserved (must be zero) $ 31 = client 0 (don't care for classes 0 and 1) 0x44244405, $ point/multicast & priority & realtime format $ 0 = O=>T fixed (1 = supported) $ 1 = O=>T variable (0 = not supported) $ 2 = T=>O fixed (1 = supported) $ 3 = T=>O variable (0 = not supported) $ 4-7 = reserved (must be zero) $ 8-10 = O=>T header (4 byte run/idle) $ 11 = reserved (must be zero) $ 12-14 = T=>O header $ 15 = reserved (must be zero) $ 16-19 = O=>T point-to-point $ 20-23 = T=>O multicast $ 24-27 = O=>T scheduled $ 28-31 = T=>O scheduled ,4,Assem20, $ O=>T RPI,Size,Format ,4,Assem70, $ T=>O RPI,Size,Format ,, $ config part 1 (dynamic assemblies) ,, $ config part 2 (module configuration) "Instance 20 70", $ connection name "", $ Help string "20 04 24 01 2C 14 2C 46"; $ exclusive output path (instance 0x70) Connection3 = 0x04010002, $ trigger & transport $ 0-15 = supported transport classes (class 1) $ 16 = cyclic (1 = supported) $ 17 = change of state (0 = not supported) $ 18 = on demand (0 = not supported) $ 19-23 = reserved (must be zero) $ 24-27 = exclusive owner $ 28-30 = reserved (must be zero) $ 31 = client 0 (don't care for classes 0 and 1) 0x44244405, $ point/multicast & priority & realtime format $ 0 = O=>T fixed (1 = supported) $ 1 = O=>T variable (0 = not supported) $ 2 = T=>O fixed (1 = supported) $ 3 = T=>O variable (0 = not supported) $ 4-7 = reserved (must be zero) $ 8-10 = O=>T header (4 byte run/idle) $ 11 = reserved (must be zero) $ 12-14 = T=>O header $ 15 = reserved (must be zero) $ 16-19 = O=>T point-to-point $ 20-23 = T=>O multicast $ 24-27 = O=>T scheduled $ 28-31 = T=>O scheduled ,6,Assem126, $ O=>T RPI,Size,Format ,6,Assem176, $ T=>O RPI,Size,Format ,, $ config part 1 (dynamic assemblies) ,, $ config part 2 (module configuration) "Instance 126 176", $ connection name "", $ Help string "20 04 24 01 2C 7E 2C B0"; $ exclusive output path (instance 0x176) Connection4 = 0x04010002, $ trigger & transport $ 0-15 = supported transport classes (class 1) $ 16 = cyclic (1 = supported) $ 17 = change of state (0 = not supported) $ 18 = on demand (0 = not supported) $ 19-23 = reserved (must be zero) $ 24-27 = exclusive owner $ 28-30 = reserved (must be zero) $ 31 = client 0 (don't care for classes 0 and 1) 0x44244405, $ point/multicast & priority & realtime format $ 0 = O=>T fixed (1 = supported) $ 1 = O=>T variable (0 = not supported) $ 2 = T=>O fixed (1 = supported) $ 3 = T=>O variable (0 = not supported) $ 4-7 = reserved (must be zero) $ 8-10 = O=>T header (4 byte run/idle) $ 11 = reserved (must be zero) $ 12-14 = T=>O header $ 15 = reserved (must be zero) $ 16-19 = O=>T point-to-point $ 20-23 = T=>O multicast $ 24-27 = O=>T scheduled $ 28-31 = T=>O scheduled ,6,Assem129, $ O=>T RPI,Size,Format ,6,Assem179, $ T=>O RPI,Size,Format ,, $ config part 1 (dynamic assemblies) ,, $ config part 2 (module configuration) "Instance 129 179", $ connection name "", $ Help string "20 04 24 01 2C 81 2C B3"; $ exclusive output path (instance 0x179) 1_PLC5C_RTD_Format1 = 1_PLC5C_1794_Discrete_RTD_Format; [Assembly] Revision = 2; Assem20 = "Instance 20", "20 04 24 14 30 03", 4,,,, 32,; Assem70 = "Instance 70", "20 04 24 47 30 03", 4,,,, 32,; Assem21 = "Instance 21", "20 04 24 15 30 03", 4,,,, 32,; Assem71 = "Instance 71", "20 04 24 46 30 03", 4,,,, 32,; Assem126 ="Instance 126", "20 04 24 7E 30 03", 6,,,, 48,; Assem176 ="Instance 176", "20 04 24 B0 30 03", 6,,,, 48,; Assem129 ="Instance 129", "20 04 24 81 30 03", 6,,,, 48,; Assem179 ="Instance 179", "20 04 24 B3 30 03", 6,,,, 48,;